  1. 26 de jul. de 2021 · The NAMUR Recommendation NE 43 has been revised and may now be obtained from the NAMUR Office. The change compared to the previous edition of NE 43 (2003-02-03) mainly concern the introduction of a safety margin for signal detection in control systems and the device behavior during initialization.

    • The Namur NE43 Recommendation
    • Out-of-range Signal Level
    • Hardware Fault Signal Level
    • Interpretation of Alarm Threshold Levels by The Control System
    • Vendor-Specific Fail-Safe Signal Levels
    • 5 Comments

    The Namur NE43 is a recommendation that gives a guideline on how a sensor fault can be indicated to a control system by means of the 4-20mA signal. It,therefore, defines two signal levels outside of the normal operation range: 1. Out-of-range level (saturation) 2. Hardware fault level

    When aninstrument is calibrated and working properly, its output signal should staybetween 4mA and 20mA for as long as process conditions are normal. Butsometimes it happens that the process conditions deviate from the normaloperation, such as the overfilling of a tank. In thiscase, a NAMUR compliant transmitter can output up to a maximum of 20.5 m...

    Smartmeasurement devices are capable of detecting internal faults, like a sensor ora converter failure. Whenthat happens, the microprocessor of a NAMUR compliant instrument will set theoutput signal to 3,6mA or 21,0mA, depending on how the user has set thefail-safe mode. A lot of smart field devices will have a fail-safe mode parameter that will le...

    Ideally, the receiving controller should have an input module with a suitable software block that can interpret the input signal within a current range between at least 0 and 22mA. By the NAMUR definition, signals between 3,6 and 3,8mA as well as between 20,5 and 21,0mA cannot occur (see white areas in the above diagram). But if for some reason the...

    Not all instrumentmanufacturers follow the NAMUR NE43 recommendation to the letter. Their self-declared“NAMUR compliant” transmitters use deviating values for the hardware faultsignal levels. The hardware fault signal levels may differ according to the transmitter type, even when these transmitters are made by the same manufacturer. This is, for in...

    deblocari usi says: 1 December 2022 at 10:32 You can certainly see your skills within the article you write. The sector hopes for more passionate writers like you who are not afraid to say how they...
    Ali says: 25 December 2022 at 07:27 I have read a few good stuff here. Definitely value bookmarking for revisiting. I’m surprised at how much attempt you make to create this wonderful, informative...
    Ute Goode says: 21 July 2023 at 11:22 Hi instrulearning.com admin, Thanks for the well-organized and comprehensive post! Reply
    Basil says: 21 March 2024 at 00:26 I would like to focus on the following: “By the NAMUR definition, signals between 3,6 and 3,8mA as well as between 20,5 and 21,0mA cannot occur (see white areas i...
  2. NAMUR NE 43 standard identifies fault 4-20mA signal which is connected from PLC or DCS control system to field transmitters or sensors.

  3. «Descubre todo lo que necesitas saber sobre NAMUR NE 43, el estándar tecnológico que revolucionará la automatización industrial. En este artículo, te sumergirás en el fascinante mundo de NAMUR NE 43 y entenderás cómo esta normativa está redefiniendo los equipos y sistemas utilizados en la industria.

  4. Hace 1 día · What exactly is Namur NE43? Namur NE43 is a commendation that offers guidance on how a sensor fault can be communicated to a control system via the 4-20mA signal.

  5. NAMUR NE 43 is a standard that defines the operating AO-LL and AO-UL values. The transmitter outputs a 4-20 mA current. However, as per NAMUR NE 43, the transmitter has it upper and lower current values.

  6. 23 de ago. de 2012 · The Namur NE43 is a recommendation which gives a guideline how a sensor fault can be indicated to a control system by means of the 4-20mA signal.