  1. NFPA 20 standard for the installation of stationary pumps for fire protection. by. National Fire Protection Association. Technical Committee on Fire Pumps. Publication date. 2012. Topics. Fire pumps -- Standards, Pompes à incendie -- Normes. Publisher. Quincy, Massachusetts : National Fire Protection Association. Collection.

  2. Stay informed and participate in the standards development process for NFPA 20

  3. Origen y desarrollo de NFPA 20 La primera norma de la National Fire Protection Association para rociadores automáticos fue publicada en 1896 y contenía párrafos sobre bombas contra incendio de vapor y rotativas.

  4. www.nfpa.org › product › nfpa-20-standardBuy NFPA 20, Standard

    Buy NFPA 20, Standard. Get the Standard for the Installation of Stationary Pumps of Fire Protection for the latest criteria for helping ensure fire pump readiness and reliability.

    • Sizing A Fire Pump
    • Selecting A Fire Pump
    • Fire Pump Pressures
    • Controllers
    • Fire Pump Design
    • Fire Pump Enclosure

    A fire pump’s size is dictated by the most hydraulically demanding area of the fire protection system. In many high-risebuildings,this canbe the automaticfirestandpipe system demandwhich requires 500gallons per minuteat 100pounds per square inchat the top of the most remote standpipe, plus 250 gpmfor each additional standpipe,up to a maximum of 1,0...

    Selection of the fire pump depends on the building infrastructure and available space.The most common choices for fire pump drivers are electric motors and diesel engines. Electric motors requiring high horsepower are commonly run on 460 volt or higher, three-phase power. Steam turbinesare also an option,but are fairly uncommon. In buildings that a...

    The total head of a fire pump is the energy imparted to the liquid as it passes through the pump, usually expressed in psi. For fire pumps such as horizontal split-case and vertical in-line centrifugal pumps that are required to operate under net positive suction head, the total head of a fire pump is calculated by adding the suction head(city pres...

    NFPA 20 requires that a fire pump be supplied bya continually available power source, usually identified asan uninterrupted power source(NFPA 20-2013, Section 9.1.5and 9.2.1). In many cases, this requirement necessitates that a backupgenerator be provided as a secondary source in the event of a power failure, in which case the fire pump controller ...

    An outside screw and yoke gate valve must be installed in the suction pipe to provide a means of isolation from the incoming supply line(NFPA 20-2013, Section 4.14.5.1). This is the only device that is explicitly permitted to be installed in the suction line within 50feetof the pump suction flange, though NFPA 20 does provide allowances for other e...

    Lastly, when determining a location for a new fire pump enclosure, it is important toconsider service accessibility and proximity to the building exterior. A fire pump room shouldbelocatedon an exterior wall adjacent to the fire lane and above the floodplain. If the enclosure must be located inside, it shallbe accessible by a passageway with a fire...

  5. NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection, 2019 edition. This standard deals with the selection and installation of pumps supplying liquid for private fire protection.

  6. La NFPA 20 es la norma que regula el diseño e instalación de las bombas contra incendios. Conoce los requisitos y las actualizaciones de esta norma.